  • www.tefbrandbeveiliging.nl Tel: 0180 - 554555
    FIRE ALARM DETECTOR
    TECHNICAL SPECIFICATIONS
    INSTALLATION
    INSTALLING THE BASE
    To ensure proper fit of the detector head to the base, all wires should be properly dressed at installation by positioning all wires flat
    against terminals and fastening the wires away from connector terminals. The detector base can be mounted directly onto most standard
    electrical junction boxes.
    INSTALLING THE HEAD
    Align detector components using provided alignment marks on both the head and base. Align detector mark and short alignment mark on
    base. Fit the detector head onto the base and twist clockwise to secure it. After all detectors are installed, apply power to the control unit .
    Test the detectors as described below.
    TESTING
    All remote signalling systems, releasing devices and extinguishing systems should be disconnected during the test period and
    reconnected at the conclusion of testing. After powering the detector, check to see the indicator LED flashing every 5 seconds. If the LED
    fails to flash, it indicates the non-functioning of the detector or fault wiring. Re-check the wiring or replace the detector if necessary.
    SMOKE: Allow smoke from a cotton wick or test smoke aerosol to enter the detector’s smoke chamber for at least 10 seconds. When
    sufficient smoke has entered, the detector will signal an alarm. This will be indicated by the illumination of the 2 Red LEDs provided. Make
    sure to clear smoke out of the chamber before resetting in order to keep the detector at its current sensitivity setting.
    HEAT: The detector to be tested should be subject to a flow of warm air at a temperature of between 65°C and 80°C. This requirement can
    be met by some domestic hair dryers. Switch on the warm airflow and check that the temperature is correct and stable. From a distance of
    several cms, direct the airflow at the guard protecting the thermistor. The detector should alarm within 60 seconds. Upon alarm
    immediately remove the heat source and check that the Red LEDs of the detector are illuminated. If a detector fails to activate within 60
    seconds, confirm connections and programming. If necessary replace unit. Note: After testing, check that the system is returned to
    normal operation. Notify the appropriate authorities that the testing procedure has been completed and the system is active again.
    MAINTENANCE
    The recommended minimum requirement for detector maintenance consists of annual cleaning of dust from the detector head using a
    low power vacuum cleaner. >> DO NOT ATTEMPT TO DISASSEMBLE THE DETECTOR
    Detector Head
    Detector Base
    Alignment Marks
    ZEOS-C
    ma_zeosc_01_010001_en_180716
    MADE IN PORTUGAL - EU
    10 V to 30 V DC
    Heat: 7 uA / Smoke: 33 uA / Smoke & Heat: 35 uA
    24 mA - Alarm LEDs
    According to EN54-5 or/and EN54-7
    0.5-2.5 mm²
    20 seconds max.
    White / ABS
    95% RH Non-Condensing
    0°C to 50°C / -10°C to 85°C
    100 mm (D) x 50 mm (H) inc. base / 144 g inc. base
    ORION, ORION MINI, ORION EX, ORION-PLUS, QUAD ZMU and ZMU
    SUPPLY VOLTAGE
    CURRENT - QUIESCENT
    CURRENT - DEVICE IN ALARM
    SENSITIVITY
    CABLE SIZE
    RESET/START-UP TIMES
    COLOUR / CASE MATERIAL
    MAX. HUMIDITY
    NORMAL / TRANSIENT OPER. TEMPERATURE
    DIMENSIONS / WEIGHT
    COMPATIBILITY
    ORDER CODE
    DESCRIPTION
    ZEOS-C-S
    ZEOS-C-H
    ZEOS-C-SH
    | CERTIFICATE |
    PHOTOELECTRIC SMOKE DETECTOR
    RATE OF RISE/FIXED TEMP HEAT DETECTOR
    MULTISENSOR SMOKE & HEAT DETECTOR
    1328-CPR-0705
    1328-CPR-0706
    1328-CPR-0704
    MECHANICAL SPECIFICATION

Need help?

Number of questions: 0

Do you have a question about the TEF ZEOS-C or do you need help? Ask your question here. Provide a clear and comprehensive description of the issue and your question. The more detail you provide for your issue and question, the easier it will be for other TEF ZEOS-C owners to properly answer your question.

View the manual for the TEF ZEOS-C here, for free. This manual comes under the category Not categorized and has been rated by 1 people with an average of a 5.1. This manual is available in the following languages: English. Do you have a question about the TEF ZEOS-C or do you need help?

TEF ZEOS-C specifications

Brand TEF
Model ZEOS-C
Product Not categorized
Language English
Filetype PDF

Related products TEF ZEOS-C

    Related product manuals

    Not categorized TEF

    Add manual

    Do you have a manual that you would like to add?