Extron OCS 100W manual

Extron OCS 100W

On this page you find the Extron OCS 100W manual. Please read the instructions in this operator manual carefully before using the product. If you have any questions about your that are not answered in the manual, please share your question in the troubleshooting section on the buttom of this page.

Brand
Extron
Model
OCS 100W
Product
Language
English
Filetype
PDF
1
IMPORTANT:
Go to www.extron.com for the
complete user guide, installation
instructions, and specifications.
Occupancy Sensor OCS 100W • Setup Guide
The OCS 100W is a wall-mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a
dual-technology sensor. The US sensor emits ultrasonic sound waves into an area and measures the speed of their return to
detect the presence of people. Frequency changes are caused by the movement of people, which is detected by the US waves.
The PIR sensor detects the presence of people based on the difference between the heat generated by moving people versus the
ambient room temperature.
The OCS 100W has a 24 VDC power input, ground/common connection, normally open/closed relay, photocell, and occupancy
output connections.
Front Panel Features
AB
1
2
3
4
1
2
3
4
Blue Timer Test Button
Blue Photocell Dial
Notch
Green Ultrasonic Range Dial
Red Infrared Sensitivity Dial
Ultrasonic
Sensors
Green LED
(status indicator)
Red LED
(status indicator)
Infrared/Photocell
Sensor and Lens
Removable Front Cove
r
DIP Switches (B)
DIP Switches (A)
Figure 1. OCS 100W Front Panel Features
Control
AB
1
2
3
4
1
2
3
4
Blue Timer Test Button
Blue Photocell Dial
Notch
Green Ultrasonic Range Dial
Red Infrar
ed Sensitivity Dial
Ultrasonic
Sensors
Green LED
(status indicator)
Red LED
(status indicator)
Infrared/Photocell
Sensor and Lens
Removable Front Cove
r
DIP Switches (B)
DIP Switches (A)
Figure 2. OCS 100W Controls
DIP Switches (B) — (see NOTE on the next page)
B OPERATION Settings
1 Timer Setting
(B1 and B2 switches
must be set together)
8 minutes:
OFF*
4 minutes:
OFF
15 minutes:
ON
30 minutes:
ON
2 OFF * ON OFF ON
B OPERATION OFF ON
3 Timer adjust Automatic Manual*
4 Sensitivity adjust Automatic Manual*
*Default
The settings for DIP Switches B3 (timer adjust) and B4 (sensitivity adjust can be set to Automatic mode or Manual mode.
Automatic mode — The sensors automatically adjust for changes in usage and seasons, eliminating the need for
manual adjustments and improving system performance.
Manual mode — The user sets the parameters of the sensors using the DIP Switches B1 and B2 set together, and
the dials.
Ultrasonic Sensors — Detect movement in the room, based on
ultrasonic waves.
Green LED (status indicator) — Flashes when the ultrasonic
sensors detect occupancy.
Infrared/Photocell Sensor and Lens — Diffracts the incoming
light and directs the light to the infrared/photocell sensor.
Red LED (status indicator) — Flashes when the infrared sensor
detects occupancy.
Removable Front Cover — Conceals all controls and DIP
switches.
1
2
DIP Switches (A)
A OPERATION OFF ON
1 Not used Not used* Not used
2 Not used Not used* Not used
3 LED indicators LEDs enabled* LEDs disabled
4 Automatic adjust
reset
Toggle to reset (Default: OFF)
*Default

Do you have a question about the Extron OCS 100W?

If you have a question about the "Extron OCS 100W", don't hesitate to ask. Make sure to describe your problem clearly, this way other users are able to provide you with the correct answer.

Buy related products:

Product specifications

Security
Sensor type   Infrared sensor
Connectivity technology Wired
Features
Mounting type   Wall
Product colour   White
Weight & dimensions
Width   71 mm
Depth   53 mm
Height   140 mm
Weight   100
Operational conditions
Operating temperature (T-T)   0 - 40
Operating relative humidity (H-H) 0 - 95
Power
Input voltage   12